Station blackout
Reactor at 100% rated thermal power. Loss of offsite power at t = 0 triggers an automatic reactor trip. Both emergency diesel generators fail to start on the undervoltage signal (common-cause fuel-system fault). Class-1E AC buses A and B remain de-energized; the plant is in station blackout. Decay heat removal is via natural circulation through the SGs with TDAFW feeding from the CST; battery-powered instrumentation supports diagnostic monitoring per ECA-0.0.
NEI 99-01's HU1 (UE) fires at t = 15 min on sustained loss of AC, HA1 (Alert) at t = 30 min, HS1 (SAE) at t = 1 hour. The scenario runs out to t = 2 hours to confirm SAE classification; recovery via FLEX strategies (NEI 12-06 portable diesel) is the assumed exit path not modeled here.
Initial state¶
{
"PT-455": 2235,
"SG-A-LVL-NR": 50,
"SG-B-LVL-NR": 50,
"SG-C-LVL-NR": 50,
"SG-D-LVL-NR": 50,
"RCS-TEMP-HOT": 612,
"BUS-A-EMERG": "LIVE",
"BUS-B-EMERG": "LIVE",
"DG-A": "STOPPED",
"DG-B": "STOPPED"
}
Injections¶
[
{ "tag": "BUS-A-EMERG", "value": "DEAD", "at-time-s": 0 },
{ "tag": "BUS-B-EMERG", "value": "DEAD", "at-time-s": 0 },
{ "tag": "DG-A", "value": "FAULT", "at-time-s": 10 },
{ "tag": "DG-B", "value": "FAULT", "at-time-s": 10 },
{ "tag": "SG-A-LVL-NR", "value": 35, "at-time-s": 1800 },
{ "tag": "RCS-TEMP-HOT", "value": 580, "at-time-s": 3600 },
{ "tag": "SG-A-LVL-NR", "value": 30, "at-time-s": 7200 }
]
Expected traversal¶
[
"E-0#verify-reactor-trip",
"E-0#verify-turbine-trip",
"E-0#verify-ac-buses",
"ECA-0.0#verify-blackout",
"ECA-0.0#establish-tdafw",
"ECA-0.0#natural-circulation",
"ECA-0.0#wait-for-ac"
]
Expected terminal state¶
{
"BUS-A-EMERG": "DEAD",
"BUS-B-EMERG": "DEAD",
"DG-A": "FAULT",
"DG-B": "FAULT",
"SG-A-LVL-NR": 30
}
EAL classification¶
Site Area Emergency (HS1) at t = 3600 s (1 hour) — both 4 kV emergency buses remain dead continuously for 1 hour. HU1 fires first at t = 900 s (UE), then HA1 at t = 1800 s (Alert), then HS1 at the 1-hour mark. The classifier returns SAE as the highest class reached.
If the scenario were extended past t = 14400 s (4 hours) with no restoration, HG1 (General Emergency) would fire. Modeling that requires either a longer time horizon or explicit injection at t = 14400 s.
References¶
- Vogtle UFSAR §15.2.6 (loss of offsite power)
- 10 CFR 50.63 (Station Blackout Rule)
- NEI 12-06 (FLEX coping strategies)
- NEI 99-01 HU1 / HA1 / HS1 / HG1 (AC-loss duration classes)
- Westinghouse-style ERG procedures E-0, ECA-0.0