Tag Catalogue¶
Generated from procedure tag definitions across the wiki. 113 unique tag IDs. Each tag is shown with its richest definition (most metadata fields populated) and every procedure that references it.
| Tag | Description | Sim path | Units | Equipment | Source | Referenced by |
|---|---|---|---|---|---|---|
| «ACCUM-1» | accumulator tank 1 (cold-leg loop 1) discharge isolation | ess.accumulator.1.discharge_valve | enum[OPEN,CLOSED] | si-system | Vogtle UFSAR §6.3.2 | ES-1.1, FR-C.1, FR-C.2 |
| «ACCUM-2» | accumulator tank 2 (cold-leg loop 2) discharge isolation | ess.accumulator.2.discharge_valve | enum[OPEN,CLOSED] | si-system | Vogtle UFSAR §6.3.2 | ES-1.1, FR-C.1, FR-C.2 |
| «ACCUM-3» | accumulator tank 3 (cold-leg loop 3) discharge isolation | ess.accumulator.3.discharge_valve | enum[OPEN,CLOSED] | si-system | Vogtle UFSAR §6.3.2 | ES-1.1, FR-C.1, FR-C.2 |
| «ACCUM-4» | accumulator tank 4 (cold-leg loop 4) discharge isolation | ess.accumulator.4.discharge_valve | enum[OPEN,CLOSED] | si-system | Vogtle UFSAR §6.3.2 | ES-1.1, FR-C.1, FR-C.2 |
| «AEJ-RAD» | condenser air-ejector radiation monitor | rad.condenser.air_ejector | cps | condenser | Vogtle UFSAR §(equipment-not-mapped) | E-3, ES-3.3 |
| «AFW-A-CV» | SG-A AFW control valve position | afw.a.cv_position | percent | afw-system | Vogtle UFSAR §10.4.9 | E-2, E-3, ECA-2.1, ES-1.1, FR-H.3, FR-H.5 |
| «AFW-B-CV» | SG-B AFW control valve position | afw.b.cv_position | percent | afw-system | Vogtle UFSAR §10.4.9 | ECA-2.1, ES-1.1, FR-H.3, FR-H.5 |
| «AFW-C-CV» | SG-C AFW control valve position | afw.c.cv_position | percent | afw-system | Vogtle UFSAR §10.4.9 | ECA-2.1, ES-1.1, FR-H.3, FR-H.5 |
| «AFW-D-CV» | SG-D AFW control valve position | afw.d.cv_position | percent | afw-system | Vogtle UFSAR §10.4.9 | ECA-2.1, ES-1.1, FR-H.3, FR-H.5 |
| «AFW-FLOW» | aggregate AFW flow (header total) | afw.header.flow | gpm | afw-system | Vogtle UFSAR §10.4.9 | ECA-0.0 |
| «AFW-PUMP-A» | motor-driven AFW pump A status | afw.pump.a.status | enum[STOPPED,RUNNING,FAULT] | afw-system | Vogtle UFSAR §10.4.9 | E-0, FR-H.1, FR-H.3, FR-H.5, FR-S.1 |
| «AFW-PUMP-B» | motor-driven AFW pump B status | afw.pump.b.status | enum[STOPPED,RUNNING,FAULT] | afw-system | Vogtle UFSAR §10.4.9 | E-0, FR-H.1, FR-H.3, FR-H.5, FR-S.1 |
| «AFW-PUMP-T» | turbine-driven AFW pump status | afw.pump.tdafw.status | enum[STOPPED,RUNNING,FAULT] | afw-system | Vogtle UFSAR §10.4.9 | E-0, ECA-0.0, FR-H.1, FR-H.3, FR-H.4, FR-H.5, FR-S.1 |
| «ARV-A» | SG-A atmospheric relief valve position | secondary.arv.a.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-a-msl | Vogtle UFSAR §10.3.2 | ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-0.2, ES-3.2, ES-3.3, FR-H.2, FR-H.4 |
| «ARV-B» | SG-B atmospheric relief valve position | secondary.arv.b.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-b-msl | Vogtle UFSAR §10.3.2 | ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-0.2, ES-3.3, FR-H.2, FR-H.4 |
| «ARV-C» | SG-C atmospheric relief valve position | secondary.arv.c.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-c-msl | Vogtle UFSAR §10.3.2 | ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-0.2, ES-3.3, FR-H.2, FR-H.4 |
| «ARV-D» | SG-D atmospheric relief valve position | secondary.arv.d.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-d-msl | Vogtle UFSAR §10.3.2 | ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-0.2, ES-3.3, FR-H.2, FR-H.4 |
| «BACKFILL-VALVE» | ruptured-SG backfill alignment valve (condensate or AFW source selector) | secondary.backfill.valve | enum[ISOLATED,AFW,CONDENSATE,FAULT] | afw-system | Vogtle UFSAR §10.4.9 | ES-3.1 |
| «BAT-LVL» | boric acid tank level | cvcs.bat.level | percent | charging-system | Vogtle UFSAR §9.3.4 | FR-S.1, FR-S.2 |
| «BLOCK-456A» | pressurizer PORV 456A block valve position | rcs.pressurizer.block.456a.position | enum[OPEN,CLOSED] | pressurizer | Vogtle UFSAR §5.4 | E-0, FR-C.1, FR-H.1 |
| «BLOCK-456B» | pressurizer PORV 456B block valve position | rcs.pressurizer.block.456b.position | enum[OPEN,CLOSED] | pressurizer | Vogtle UFSAR §5.4 | E-0, FR-C.1, FR-H.1 |
| «BLOWDOWN-A» | SG-A blowdown isolation valve position | secondary.blowdown.a.position | enum[OPEN,CLOSED] | sg-a | Vogtle UFSAR §10.3 | E-2, E-3, ES-3.2 |
| «BORATE-FLOW» | emergency boration flow rate | cvcs.borate.flow | gpm | charging-system | Vogtle UFSAR §9.3.4 | FR-S.1, FR-S.2 |
| «BUS-A-EMERG» | emergency 4kV bus A energization status | electrical.bus.emerg_a.energized | bool | bus-a-emerg | Vogtle UFSAR §8.3 | E-0, ECA-0.0, ES-0.0 |
| «BUS-B-EMERG» | emergency 4kV bus B energization status | electrical.bus.emerg_b.energized | bool | bus-b-emerg | Vogtle UFSAR §8.3 | E-0, ECA-0.0, ES-0.0 |
| «CCW-RAD» | component cooling water outlet radiation monitor (letdown HX outlet) | rad.ccw.let_hx_outlet | rem_per_hr | rad-monitoring | Vogtle UFSAR §11.5 | ECA-1.2 |
| «CET-AVG» | core-exit thermocouple average (5+ representative locations across the core) | rcs.core_exit.thermocouple.avg | degF | rcs | Vogtle UFSAR §7.5 | ECA-3.2, ES-1.4, FR-C.1, FR-C.2, FR-C.3, FR-Z.3 |
| «CHG-FLOW» | charging flow rate | cvcs.charging.flow | gpm | charging-system | Vogtle UFSAR §9.3.4 | ECA-2.1, ES-0.2, ES-1.1, ES-1.2, FR-I.1, FR-I.2 |
| «CHG-PUMP-A» | charging pump A status | cvcs.charging_pump.a.status | enum[STOPPED,RUNNING,FAULT] | charging-system | Vogtle UFSAR §9.3.4 | E-0, FR-C.1, FR-C.2, FR-I.1, FR-I.2, FR-S.1, FR-S.2 |
| «CHG-PUMP-B» | charging pump B status | cvcs.charging_pump.b.status | enum[STOPPED,RUNNING,FAULT] | charging-system | Vogtle UFSAR §9.3.4 | E-0, FR-C.1, FR-C.2, FR-I.1, FR-I.2, FR-S.1, FR-S.2 |
| «CONDENSER-VAC» | condenser vacuum (absolute pressure) | secondary.condenser.vacuum | inhga | secondary | Vogtle UFSAR §10.4.1 | FR-H.4 |
| «CSPRAY-A» | containment spray pump A status | ess.cspray_pump.a.status | enum[STOPPED,RUNNING,FAULT] | containment-spray | Vogtle UFSAR §6.2.2 | E-0, ECA-1.1, FR-Z.1, FR-Z.2, FR-Z.3 |
| «CSPRAY-B» | containment spray pump B status | ess.cspray_pump.b.status | enum[STOPPED,RUNNING,FAULT] | containment-spray | Vogtle UFSAR §6.2.2 | E-0, ECA-1.1, FR-Z.1, FR-Z.2, FR-Z.3 |
| «CST-LVL» | condensate storage tank level | secondary.cst.level | percent | afw-system | Vogtle UFSAR §10.4.9 | FR-H.5 |
| «CTMT-NG» | containment noble-gas activity monitor | rad.containment.noble_gas | uCi_per_cc | containment | Vogtle UFSAR §11.5 | FR-Z.3 |
| «CTMT-PR» | containment building pressure | containment.pressure | psig | containment | Vogtle UFSAR §6.2 | E-0, E-1, ECA-1.2, ES-0.0, FR-Z.1, FR-Z.2 |
| «CTMT-RAD» | containment area radiation monitor | rad.containment.high_range | rem_per_hr | containment | Vogtle UFSAR §6.2 | E-1, ES-0.0, ES-0.1, FR-Z.1, FR-Z.3 |
| «CTMT-SUMP-LVL» | containment recirculation sump level | containment.sump.level | percent | containment | Vogtle UFSAR §6.2 | E-1, ECA-1.2, ES-0.0, ES-1.3, FR-C.1, FR-H.1, FR-Z.2 |
| «CTMT-TEMP» | containment average temperature | containment.temperature.avg | degF | containment | Vogtle UFSAR §6.2 | FR-Z.2 |
| «DC-BUS-LVL» | vital DC bus voltage (representative) | electrical.dc_bus.voltage | volts_dc | dc-bus | Vogtle UFSAR §8.3.2 | ECA-0.0 |
| «DG-A» | emergency diesel generator A status | electrical.dg.a.status | enum[STOPPED,STARTING,RUNNING,LOADED,FAULT] | emergency-dg-a | Vogtle UFSAR §8.3.1.1 | E-0, ECA-0.0 |
| «DG-B» | emergency diesel generator B status | electrical.dg.b.status | enum[STOPPED,STARTING,RUNNING,LOADED,FAULT] | emergency-dg-b | Vogtle UFSAR §8.3.1.1 | E-0, ECA-0.0 |
| «HL-FLOW» | hot-leg injection header flow | ess.hl_inject.header_flow | gpm | si-system | Vogtle UFSAR §6.3.2 | ES-1.4 |
| «HL-INJECT-A» | hot-leg injection train A alignment | ess.hl_inject.a.alignment | enum[ISOLATED,ALIGNED,FAULT] | si-system | Vogtle UFSAR §6.3.2 | ES-1.4 |
| «HL-INJECT-B» | hot-leg injection train B alignment | ess.hl_inject.b.alignment | enum[ISOLATED,ALIGNED,FAULT] | si-system | Vogtle UFSAR §6.3.2 | ES-1.4 |
| «HV-LINE» | reactor vessel head vent line position / activity | rcs.head_vent.line | enum[ISOLATED,VENTING,FAULT] | rcs | Vogtle UFSAR §5.4 (head vent per NUREG-0737 II.B.1) | FR-I.3 |
| «LET-FLOW» | letdown flow rate | cvcs.letdown.flow | gpm | charging-system | Vogtle UFSAR §9.3.4 | ECA-2.1, ES-1.1, FR-I.1, FR-I.2 |
| «LET-ISOL» | CVCS letdown isolation valve | cvcs.letdown.isolation | enum[OPEN,CLOSED] | charging-system | Vogtle UFSAR §9.3.4 | ECA-1.2 |
| «LO-HEAD-FLOW» | low-head SI / RHR header flow | ess.lo_head.header_flow | gpm | si-system | Vogtle UFSAR §6.3 | ECA-1.1, ES-1.3 |
| «MAB-RAD» | main auxiliary building area radiation monitor | rad.mab.area | rem_per_hr | rad-monitoring | Vogtle UFSAR §11.5 | ECA-1.2, ES-3.2 |
| «MFW-A-CV» | SG-A main feedwater control valve position | secondary.mfw.a.cv_position | percent | mfw-system | Vogtle UFSAR §10.4.7 | E-2, E-3, FR-H.1 |
| «MS-HEADER-PR» | main steam header pressure | secondary.ms_header.pressure | psig | secondary | Vogtle UFSAR §10.3 | ECA-2.1 |
| «MSIV-A» | SG-A main steam isolation valve position | secondary.msiv.a.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-a-msl | Vogtle UFSAR §11.5 | E-2, E-3 |
| «MSIV-B» | SG-B main steam isolation valve position | secondary.msiv.b.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-b-msl | Vogtle UFSAR §11.5 | E-2, E-3 |
| «MSIV-C» | SG-C main steam isolation valve position | secondary.msiv.c.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-c-msl | Vogtle UFSAR §11.5 | E-2, E-3 |
| «MSIV-D» | SG-D main steam isolation valve position | secondary.msiv.d.position | enum[OPEN,CLOSED,INTERMEDIATE] | sg-d-msl | Vogtle UFSAR §11.5 | E-2, E-3 |
| «N2-SUPPLY» | ARV nitrogen-supply pressure | secondary.arv.n2_supply.pressure | psig | arv-system | Vogtle UFSAR §10.3.2 | FR-H.4 |
| «NAOH-LVL» | containment-spray sodium hydroxide additive tank level | ess.cspray.additive_tank.level | percent | containment-spray | Vogtle UFSAR §6.2.2 | FR-Z.1 |
| «NIS-IR» | nuclear instrumentation intermediate range | nis.intermediate_range.avg | amps | nuclear-instrumentation | Vogtle UFSAR §7.7 | FR-S.1 |
| «NIS-PR-AVG» | nuclear instrumentation power-range average (4-channel) | nis.power_range.avg | percent | nuclear-instrumentation | Vogtle UFSAR §7.7 | E-0, FR-S.1 |
| «NIS-SR» | nuclear instrumentation source range count rate | nis.source_range.count_rate | cps | nuclear-instrumentation | Vogtle UFSAR §7.7 | FR-S.1, FR-S.2 |
| «PHASE-B-SIG» | containment Phase B isolation signal (latched) | ess.phase_b.actuation_signal | bool | containment | Vogtle UFSAR §6.2 | E-0, FR-Z.1 |
| «PORV-456A» | pressurizer PORV 456A position | rcs.pressurizer.porv.456a.position | enum[OPEN,CLOSED,INTERMEDIATE] | pressurizer | Vogtle UFSAR §5.4 | E-0, E-3, ECA-3.1, ECA-3.3, ES-0.2, ES-1.2, FR-C.1, FR-H.1, FR-I.3, FR-P.1 |
| «PORV-456B» | pressurizer PORV 456B position | rcs.pressurizer.porv.456b.position | enum[OPEN,CLOSED,INTERMEDIATE] | pressurizer | Vogtle UFSAR §5.4 | E-0, E-3, ECA-3.1, ECA-3.3, ES-0.2, ES-1.2, FR-C.1, FR-H.1, FR-I.3, FR-P.1 |
| «PRIMARY-WATER-VALVE» | primary water makeup isolation valve | cvcs.primary_water.makeup_valve | enum[OPEN,CLOSED] | charging-system | Vogtle UFSAR §9.3.4 | FR-S.2 |
| «PT-455» | pressurizer pressure (wide range) | rcs.pressurizer.pressure_wr | psig | pressurizer | Vogtle UFSAR §5.4 | E-0, E-1, E-3, ECA-0.0, ECA-1.1, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-0.0, ES-0.1, ES-1.1, ES-1.2, ES-3.1, FR-C.1, FR-C.3, FR-H.1, FR-I.1, FR-I.2, FR-P.1, FR-P.2, FR-S.2, FR-Z.2 |
| «PZR-HTR» | pressurizer heater bank energization status | rcs.pressurizer.heaters.status | enum[OFF,ON,FAULT] | pressurizer | Vogtle UFSAR §5.4 | ECA-2.1, ECA-3.3, ES-1.2, FR-P.1, FR-P.2 |
| «PZR-LVL» | pressurizer level | rcs.pressurizer.level | percent | pressurizer | Vogtle UFSAR §5.4 | ECA-0.0, ECA-3.1, ECA-3.2, ES-0.1, ES-0.2, ES-1.1, ES-1.2, FR-I.1, FR-I.2 |
| «RCP-1» | reactor coolant pump 1 status | rcs.rcp.1.status | enum[STOPPED,RUNNING,FAULT] | rcp-1 | Vogtle UFSAR §5.4.1 | E-1, ECA-2.1 |
| «RCP-2» | reactor coolant pump 2 status | rcs.rcp.2.status | enum[STOPPED,RUNNING,FAULT] | rcp-2 | Vogtle UFSAR §5.4.1 | E-1, ECA-2.1 |
| «RCP-3» | reactor coolant pump 3 status | rcs.rcp.3.status | enum[STOPPED,RUNNING,FAULT] | rcp-3 | Vogtle UFSAR §5.4.1 | E-1, ECA-2.1 |
| «RCP-4» | reactor coolant pump 4 status | rcs.rcp.4.status | enum[STOPPED,RUNNING,FAULT] | rcp-4 | Vogtle UFSAR §5.4.1 | E-1, ECA-2.1 |
| «RCS-BORON» | RCS boron concentration (sampled) | rcs.boron.concentration | ppm | rcs | Vogtle UFSAR §9.3.4 | ES-1.4, FR-S.2 |
| «RHR-HX» | RHR heat-exchanger outlet temperature (representative) | ess.rhr.hx_outlet_temp | degF | rhr-system | Vogtle UFSAR §5.4.7 | ES-1.3 |
| «RHR-ISOL» | RHR system isolation valve (representative) | ess.rhr.isolation_valve | enum[OPEN,CLOSED] | rhr-system | Vogtle UFSAR §5.4.7 | ECA-1.2 |
| «RHR-PUMP-A» | residual heat removal pump A status | ess.rhr_pump.a.status | enum[STOPPED,RUNNING,FAULT] | rhr-system | Vogtle UFSAR §5.4.7 | ECA-1.1, ES-1.3 |
| «RHR-PUMP-B» | residual heat removal pump B status | ess.rhr_pump.b.status | enum[STOPPED,RUNNING,FAULT] | rhr-system | Vogtle UFSAR §5.4.7 | ECA-1.1, ES-1.3 |
| «ROD-POS-AVG» | average control rod bottom position | rcs.rod.position.avg | steps_withdrawn | rod-control-system | Vogtle UFSAR §7.7 | FR-S.1, FR-S.2 |
| «RT-PB» | reactor trip pushbutton (front-panel) state | rps.manual_trip.pushbutton | enum[NORMAL,DEPRESSED] | reactor-protection-system | Vogtle UFSAR §7.2 | FR-S.1 |
| «RVLS-DYN» | reactor vessel level indication system, dynamic-pressure-compensated channel | rcs.rvls.dynamic.level | percent_collapsed_liquid | rcs | Vogtle UFSAR §7.5 | ECA-3.2, FR-C.1, FR-C.2, FR-C.3, FR-I.2, FR-I.3 |
| «RWST-LVL» | refueling water storage tank level | rwst.level | percent | rwst | Vogtle UFSAR §6.3.2 | E-1, ECA-1.1, ES-1.2, ES-1.3, FR-C.2, FR-H.1, FR-Z.2 |
| «SG-A-LVL-NR» | SG-A narrow-range level | secondary.sg.a.level_nr | percent | sg-a | Vogtle UFSAR §10.3 | E-0, E-1, E-2, E-3, ES-0.0, ES-0.1, ES-1.1, FR-H.1, FR-H.3, FR-H.5 |
| «SG-A-N16» | SG-A main steam line N-16 radiation monitor | rad.msl.a.n16 | cps | sg-a-msl | Vogtle UFSAR §11.5 | E-0, E-2, E-3, ES-0.0, ES-3.1, FR-H.3 |
| «SG-A-PR» | SG-A steam pressure | secondary.sg.a.steam_pressure | psig | sg-a | Vogtle UFSAR §10.3 | E-2, E-3, ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ES-0.0, ES-3.1, ES-3.3, FR-H.2, FR-H.4 |
| «SG-B-LVL-NR» | SG-B narrow-range level | secondary.sg.b.level_nr | percent | sg-b | Vogtle UFSAR §10.3 | E-0, E-1, E-2, E-3, ES-0.0, ES-0.1, ES-1.1, FR-H.1, FR-H.3, FR-H.5 |
| «SG-B-N16» | SG-B main steam line N-16 radiation monitor | rad.msl.b.n16 | cps | sg-b-msl | Vogtle UFSAR §11.5 | E-0, E-2, E-3, ES-0.0, ES-3.1, FR-H.3 |
| «SG-B-PR» | SG-B steam pressure | secondary.sg.b.steam_pressure | psig | sg-b | Vogtle UFSAR §10.3 | E-2, E-3, ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ES-0.0, ES-3.1, ES-3.3, FR-H.2, FR-H.4 |
| «SG-C-LVL-NR» | SG-C narrow-range level | secondary.sg.c.level_nr | percent | sg-c | Vogtle UFSAR §10.3 | E-0, E-1, E-2, E-3, ES-0.0, ES-0.1, ES-1.1, FR-H.1, FR-H.3, FR-H.5 |
| «SG-C-N16» | SG-C main steam line N-16 radiation monitor | rad.msl.c.n16 | cps | sg-c-msl | Vogtle UFSAR §11.5 | E-0, E-2, E-3, ES-0.0, ES-3.1, FR-H.3 |
| «SG-C-PR» | SG-C steam pressure | secondary.sg.c.steam_pressure | psig | sg-c | Vogtle UFSAR §10.3 | E-2, E-3, ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ES-0.0, ES-3.1, ES-3.3, FR-H.2, FR-H.4 |
| «SG-D-LVL-NR» | SG-D narrow-range level | secondary.sg.d.level_nr | percent | sg-d | Vogtle UFSAR §10.3 | E-0, E-1, E-2, E-3, ES-0.0, ES-0.1, ES-1.1, FR-H.1, FR-H.3, FR-H.5 |
| «SG-D-N16» | SG-D main steam line N-16 radiation monitor | rad.msl.d.n16 | cps | sg-d-msl | Vogtle UFSAR §11.5 | E-0, E-2, E-3, ES-0.0, ES-3.1, FR-H.3 |
| «SG-D-PR» | SG-D steam pressure | secondary.sg.d.steam_pressure | psig | sg-d | Vogtle UFSAR §10.3 | E-2, E-3, ECA-0.0, ECA-2.1, ECA-3.1, ECA-3.2, ES-0.0, ES-3.1, ES-3.3, FR-H.2, FR-H.4 |
| «SI-FLOW» | high-head SI header flow | ess.si.header_flow | gpm | si-system | Vogtle UFSAR §6.3 | ES-1.3 |
| «SI-PUMP-A» | high-head SI pump A status | ess.si_pump.a.status | enum[STOPPED,RUNNING,FAULT] | si-system | Vogtle UFSAR §6.3 | E-0, E-1, ECA-1.2, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-1.1, ES-1.3, FR-C.1, FR-C.2, FR-H.1, FR-I.3, FR-P.1, FR-P.2 |
| «SI-PUMP-B» | high-head SI pump B status | ess.si_pump.b.status | enum[STOPPED,RUNNING,FAULT] | si-system | Vogtle UFSAR §6.3 | E-0, E-1, ECA-1.2, ECA-2.1, ECA-3.1, ECA-3.2, ECA-3.3, ES-1.1, ES-1.3, FR-C.1, FR-C.2, FR-H.1, FR-I.3, FR-P.1, FR-P.2 |
| «SI-SIG» | safety injection actuation signal (latched) | ess.si.actuation_signal | bool | si-system | Vogtle UFSAR §6.3 | E-0, E-1, FR-I.2 |
| «SPRAY-FLOW» | containment spray total flow (header) | ess.cspray.header_flow | gpm | containment-spray | Vogtle UFSAR §6.2.2 | FR-Z.1, FR-Z.2 |
| «STEAM-DUMP» | condenser steam dump availability (auto-permissive flag) | secondary.steam_dump.available | bool | secondary | Vogtle UFSAR §10.4.4 | ES-1.2, ES-3.3, FR-H.4 |
| «SUB-MARGIN» | RCS subcooling margin (T_sat at PT-455 minus hot-leg temperature) | rcs.subcooling_margin | degF | rcs | Vogtle UFSAR §15.6 | E-0, E-1, ECA-0.0, ECA-1.2, ECA-3.1, ECA-3.2, ES-0.1, ES-0.2, ES-1.1, ES-1.2, ES-1.3, ES-1.4, FR-C.1, FR-C.2, FR-C.3, FR-H.1, FR-I.2, FR-I.3, FR-P.1, FR-S.2 |
| «SUMP-SCREEN-DP» | containment sump strainer differential pressure | ess.sump.strainer.dp | psid | si-system | Vogtle UFSAR §6.3.2 | ECA-1.1, ES-1.3 |
| «TAVG» | RCS average temperature (4-loop average) | rcs.t_avg | degF | rcs | Vogtle UFSAR §5.1.1 | ES-0.1, ES-1.1 |
| «TDAFW-SPEED» | turbine-driven AFW pump turbine speed | afw.tdafw.turbine_speed | rpm | afw-system | Vogtle UFSAR §10.4.9 | ECA-0.0 |
| «TE-411-COLD» | RCS loop 1 cold-leg temperature | rcs.loop1.t_cold | degF | rcs-loop-1 | Vogtle UFSAR §5.1.1 | E-1, E-2, ECA-0.0, ECA-2.1, ECA-3.3, ES-0.2, ES-1.2, FR-P.1, FR-P.2 |
| «TE-411-HOT» | RCS loop 1 hot-leg temperature | rcs.loop1.t_hot | degF | rcs-loop-1 | Vogtle UFSAR §5.1.1 | E-1, E-3, ECA-0.0, ES-0.2, FR-H.1 |
| «TE-421-COLD» | RCS loop 2 cold-leg temperature | rcs.loop2.t_cold | degF | rcs-loop-2 | Vogtle UFSAR §5.1.1 | E-2, ECA-0.0, ES-0.2, FR-P.1, FR-P.2 |
| «TE-421-HOT» | RCS loop 2 hot-leg temperature | rcs.loop2.t_hot | degF | rcs-loop-2 | Vogtle UFSAR §5.1.1 | ECA-0.0, ES-0.2 |
| «TE-431-COLD» | RCS loop 3 cold-leg temperature | rcs.loop3.t_cold | degF | rcs-loop-3 | Vogtle UFSAR §5.1.1 | E-2, ECA-0.0, ES-0.2, FR-P.1, FR-P.2 |
| «TE-431-HOT» | RCS loop 3 hot-leg temperature | rcs.loop3.t_hot | degF | rcs-loop-3 | Vogtle UFSAR §5.1.1 | ECA-0.0, ES-0.2 |
| «TE-441-COLD» | RCS loop 4 cold-leg temperature | rcs.loop4.t_cold | degF | rcs-loop-4 | Vogtle UFSAR §5.1.1 | E-2, ECA-0.0, ES-0.2, FR-P.1, FR-P.2 |
| «TE-441-HOT» | RCS loop 4 hot-leg temperature | rcs.loop4.t_hot | degF | rcs-loop-4 | Vogtle UFSAR §5.1.1 | ECA-0.0, ES-0.2 |
| «TRIP-BKR-A» | reactor trip breaker A position | rps.trip_breaker.a.position | enum[OPEN,CLOSED] | reactor-protection-system | Vogtle UFSAR §7.2 | E-0, FR-S.1 |
| «TRIP-BKR-B» | reactor trip breaker B position | rps.trip_breaker.b.position | enum[OPEN,CLOSED] | reactor-protection-system | Vogtle UFSAR §7.2 | E-0, FR-S.1 |